Difference between version 58 and version 51:
Lines 7-8 were replaced by lines 7-8
- is a cone. Perpendicular to the field direction, the acces is +-6.7 deg on
- a 15 mm sample.
+ is a cone. Perpendicular to the field direction, the access is +-6.7 deg on
+ a 15 mm sample, or 65 mm parallel access.
At line 27 added 1 line.
+ [MA7/asysym.jpg]
Line 30 was replaced by line 31
- For changing for symmetric mode to asymmetric and vice versa:
+ For changing from symmetric mode to asymmetric mode and vice versa:
Lines 32-33 were replaced by lines 33-37
- * on the top of the magnet under the aluminium cyclinder
- ** one cable can be switched between the ASY and SYM marked connection
+ * on the top of the magnet under the aluminium cyclinder:
+ ** make sure that the magnetic field is zero (IPS: shown current is 0 AND "persistent mode" LED is off)
+ ** switch the magnet power supply IPS off
+ ** open the cap using the screws marked on the picture above
+ ** switch the cable from the SYM pin to ASY pin (or vice versa)
At line 34 added 2 lines.
+ ** close the cap
+ ** switch the magnet power supply on

Back to MA7, or to the Page History.