Diff: HEOX

Search SINQ Wiki:
SINQ LIN

SINQ Wiki
- Main Page
- Search SINQ Wiki
- Sample Environment
- Probenumg. Intern
- Troubleshooting SICS

This Page
- Page Info
- Printer Friendly

Referenced by
DilutionCryostats

Wiki Info
- Unused pages
- Undefined pages
- RecentChanges
- Page Index
- System Info
- JSPWiki Docu
- SandBox
- OneMinuteWiki
- Create a New Page




JSPWiki v2.0.52


Difference between version 16 and version 15:
Line 30 was replaced by line 30
- Settings:
+ LS340 Settings:
At line 50 added 3 lines.
+ You can operate the system by regulating the Sorb and the 3He-pot temperature independently (controlmode 0)
+ or by using both heaters cooperatively to control the 3He-pot temperature (controlmode 1) in this case the setpoints
+ for both loops should have the same value.
At line 51 added 4 lines.
+ !INPORTANT: both heaters are disabled if any setpoint is exactly zero. In order to control the Temperature using only
+ 1 heater the other set value should be small (not reachable)
+
+
Line 54 was replaced by line 61
- ''tt controlmode <n>'' ...sets control channel of loop 1 to B (n=1) or D (n=0)
+ ''tt controlmode <n>'' ...sets control channel of loop 1 to B (n=0) or D (n=01)
Line 62 was replaced by line 69
- (e.g. tt send cset 2:D,1,1 sets loop 2 to control the He-3 pot heater
+ (e.g. tt send cset 2:D,1,1 sets loop 2 to control the 3He-pot heater

Back to HEOX, or to the Page History.