At line 32 added 15 lines.
+ __Operation with two heaters:__
+ Heox starts up with the second PID loop (Analog Out2) enabled
+ and loop 1 to control the temperature of the Sorb (Ch B)
+
+ __sea_commands__
+
+ ''tt controlmode'' <n> ...sets control channel of loop 1 to B (n=1) or D (n=0)
+ ''tt set2'' <n.n> ... setpoint of loop 2 in K
+ ''tt send pid'' n:P,I,D ... set PID values of loop n (1 or 2)
+ ''tt send cset'' n:<channel>,<unit>,<off/on>,<power enable> sets the channel (A,B,C,D)
+ which will be used by loop <n>
+ (e.g. tt send cset 2:D,1,1 sets loop 2 to control the He-3 pot heater
+ ''tt send pid?n'' query PID settings of loop n
+ ''tt send cset?n'' query control settings of loop n
+