Common Parameters and Subcommands for all EASE Objects
Command Syntax Description Defined by[2]
Standard commands defined for all objects based on pardef:
<obj> list c make a list of most important parameters (all parameters defined with a call to ParTail and not ParList, or with a call to ParList(NULL)
<obj> list all c make a full list of all parameters
<obj> list <group> c make a list of only a group of parameters (all parameters defined with a call to ParList("<group>") )
<obj> log <par> c switch the logger on for parameter <par> (on for parameters defined without an explicit call to ParSwitch(NULL) )
<obj> log <par> <sugar> c switch the logger on for parameter <par>, giving a sugar name (see [SicsSugar])
<obj> unlog <par> c switch the logger off for parameter <par>
<obj> sugar c return a list of sugar parameters
<obj> save <par> c switch on status file saving for parameter <par> (on for changeable parameters, or explicitley when defined with a call to ParSave
<obj> unsave <par> c switch off status file saving for parameter <par>
<obj> interest c switch interest callback on (every change will be notified to the executive client)
<obj> uninterest c switch interest callback off
Parameters defined in ParStdDef
<obj> verbose w verbosity. 0 is quiet, 1 is standard, 2 is verbose (logging all serial communication)
<obj> driver r driver name
<obj> creationCmd r command to create this object
Parameter defined by EaseBasePar
<obj> restart c reconnect serial connection
Parameter defined by EaseSendPar
<obj> send <command> c send a serial command. Warning: the resonse is delayed and can therefore not be used in scripts.
Parameters defined by EaseDrivPar
<obj> upperLimit w upper limit of target value
<obj> lowerLimit w lower limit of target value
<obj> tolerance w tolerance
<obj> maxwait w maximal time to wait for target value (sec) or 0 for infinite wait
<obj> settle w time to wait after target value is within tolerance
<obj> targetValue r target value
Parameter defined by EaseMsgPar
<obj> status r connection status of the device (empty when normal)
c: command, r: read-only parameters, w: writeable parameter